Albatech

Albatech APL Monofase

6�2 Albatech APL Monofase

Easy Installation

Termination

Addressing

Interface

No

Jumper

Yes

RS485

APL Monofase 2�0/3�0/4�0/5�0

Inverters from different Albatech model ranges (APL monophase / triphase) cannot be mixed on an RS485

connection. The correct range must be selected when selecting inverters.

Overview

Interface not integrated; Upgrade the Albatech RS485 interface

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Install the RS485 interface in the inverter

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Installing the RS485 interface
Procedure

► Install the RS485 interface in the inverter in accordance with the interface card installation instructions.

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made, shielded 3 wire data cable and terminal block connector.

Procedure

1.

Open the inverter as shown in the inverter‘s instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► Pin 2 - D+

► 3

► Pin 3 - GND

► 4

► Pin 1 - D-

3. If only one inverter is to be connected this must be terminated.

Set the jumper on the RS485 interface card to ON.

4. Close the inverter if no other inverters are to be connected.

5. Insert the terminal block connector into the Solar-Log™ RS485 socket.