Solare Datensysteme Solar-Log User Manual

Page 240

Advertising
background image

240

SolarMax

SolarMax – Cx series

Connect the inverters to each other

Connect using a network cable (patch cable)

Where to connect: RJ45 socket inside the inverter (on the retrofitted RS485 interface)

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Insert the RJ45 plug into any RJ45 socket on inverter 1.

3. Insert the other end of the wire into any RJ45 socket on inverter 2.

4. Connect the other inverters to each other in the same way.

5. Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Setting: Using the inverter operating display

Procedure: Start according to the inverter's instructions

Note for feed-in management

The inverter itself has to be configured with MaxTalk2 (SolarMax's software) and set to
"Remote mode" to be able to use reactive power management. Please refer to the inverter
instructions for more information on this topic.