Eltek

Eltek central inverter

27�2 Eltek central inverter

Easy Installation

Termination

Addressing

Interface

No

DIP switch

Yes

RS485

Select "Eltek Central" during the inverter detection

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

3-pin wiring

The communication address has to be assigned (1 - 247)

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Configure the inverter's communication interface

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 3 wire data cable and terminal block connector.

Procedure

1.

Connect wires as shown in the diagram below.

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► X12.1 A (Data +)

► 3

► X12.3 GND

► 4

► X12.2 B (Data -)

2. If only one inverter is to be connected, it must be terminated according to the manufacturer's instruc-

tions.

3. Close the inverter cover if no other inverters are to be connected.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

The inverters are connected together using the RS485 interface. Refer to the manufacturer's inverter ma-

nual for the details on how to setup the connection.

Allocate communication address

Recommendation: Continuous numbering starting with 1 going to 247

Setting: Using the inverter operating display

Procedure: Start according to the inverter's instructions