64 refusol – Solare Datensysteme Solar-Log User Manual

Page 183

Advertising
background image

183

REFUSOL

REFUSOL

64 REFUSOL

64�1 REFUSOL

Easy Installation

Termination

Addressing

Interface

Yes

Terminating plug

Yes

RS485

Overview

Integrated interface

Where to connect: RJ45 socket on the bottom of the inverter

2-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Instructions for older Solar-Log™/ Refu installations

Set compatibility

Note

To use active and reactive power management, all of the inverters need to be set to:

Protocol 1

57600 baud

Parameter 1164 = 2

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 2 wire data cable and terminal block connector.

Procedure

1.

Connect wires as shown in the diagram below.

Solar-Log™ terminal strip connector

RS485 inverter socket

Terminal

PIN

► 1

► 2

► 4

► 3

2. If only one inverter is to be connected this must be terminated.

On the sockets "RS485 OUT" with REFUSOL round plugs bypass the connections PIN1 to PIN2 and

PIN3 to PIN4.

3. Close the inverter if no other inverters are to be connected.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.