Solare Datensysteme Solar-Log User Manual

Page 44

Advertising
background image

44

AROS Solar Technology

AROS Solar Technology (RS485)

8�2 AROS Solar Technology (RS485)

Easy Installation

Termination

Addressing

Interface

No

Yes

No

RS485

Select "Aros 485" during the inverter detection

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

3-pin wiring

Communication address does not have to be assigned

Note:

The order in which the inverters are displayed in the Solar-Log™ after detection is random.
We strongly recommend that you change the order of the inverters immediately after de-
tection at startup in the

Configuration | Device | Configuration | Order

menu box.

The inverters can be identified using the displayed serial number.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Connect inverters to the Solar-Log™

The wiring is done using a

self-made cable connection with terminal block connector.

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

► A (+)

► 3

► GND

► 4

► B (-)

2. If only one inverter is to be connected terminate this in accordance with the inverter instructions.

3. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a 3 wire, shielded data cable

Where to connect: Terminal strip inside the inverter