The following types are to be connected according to this diagram:

PVI 10KW

PVI 13KW

PVI 15KW

PVI 100KW

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Change the communication address if required.

Every address may only be used once.

Address range 1 to 16.

Connect inverters to the Solar-Log™

The wiring is done using a

self-made cable connection with terminal block connector.

Where to connect: Terminal strip inside the inverter

Procedure

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

Terminal strip inside the inverter

Terminal

PIN

► 1 (Data+)

RS485 A

► 3 (Ground)

RS485 G

► 4 (Data-)

RS485 B

If only one inverter is to be connected, according to the manufacturer's handbook it must be termi-
nated.

Insert the terminal block connector into the Solar-Log™ RS485 socket.