295

Voltwerk

Voltwerk (only Solar-Log 1000 and 2000)

Connecting inverters to each other (only Solar-Log 1000 and 2000)

Connection is made only with a ready-made data cable specially for connecting the inverters to
each other (optional extra: not supplied).

Where to connect: CAN socket outside the inverter.

Procedure

1.

Insert the CAN plug into any CAN OUT socket on inverter 1.

2. Insert the other end of the wire into any CAN IN socket on inverter 2.

3. Connect the other inverters to each other in the same way.

4. Terminate in the last inverter.

Insert the two 5 pin 120

Ω terminal resistors from the ready-made cable set into the CAN OUT socket.