71�3 schneider electric conext – Solare Datensysteme Solar-Log User Manual

Page 202

Advertising
background image

202

Schneider Electric

Schneider Electric Conext

71�3 Schneider Electric Conext

Easy Installation

Termination

Addressing

Interface

No

-

Yes

RS485

Overview

Integrated interface

Where to connect: RJ45 socket on the outside of the inverter

3-pin wiring

Communication address must be allocated.

Installation steps

Allocate communication address

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Connect inverters to the Solar-Log™

The wiring is done using a

self-made cable connection with RS485 data cable and terminal block connector.

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Insert the RJ45 plug into any RJ45 socket on the first inverter.

3. If you are making the cable yourself, connect the wires as shown in the following diagram

4. If only one inverter is to be connected this must be terminated.

Solar-Log™ terminal strip connector

Inverters

Terminal

PIN

► 1

► 4

► 3

► 8

► 4

► 5

5. Close the inverter if no other inverters are to be connected.

6. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Connect the inverters to each other

Connect using a network cable (patch cable)

Where to connect: 2 RJ45 sockets