Zentral Solar Deutschland ZSD

Zentral Solar Deutschland ZSD - zentralpower

102�2 Zentral Solar Deutschland ZSD - zentralpower

Easy Installation

Termination

Addressing

Interface

No

-

Yes

RS485

Overview

Integrated interface

Where to connect: RJ45 socket on the outside of the inverter

2-pin wiring

The communication addresses (1-247) have to be assigned

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 2 wire data cable with a RJ45 socket and a terminal block connector.

Procedure

1.

If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ 45 socket

Terminal

PIN

► 1

► 4 (+)

► 4

► 3 (-)

2. Insert the RJ45 plug into the RJ45 socket on the inverter.

3. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Wiring using 2 pin cable with round plugs.

Where to connect: Round sockets on the outside of the inverter.

Procedure

1.

Insert the RJ45 plug into the RJ45 socket on the first inverter.

2. Insert the other end of the wire into any RJ45 socket on inverter 2.

3. Connect the other inverters to each other in the same way.

4. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Address range: 1 - 247

Setting: Using the inverter operating display

Procedure: Start according to the inverter's instructions