SolarMax

SolarMax – Cx series

79�2 SolarMax – Cx series

Easy Installation

Termination

Addressing

Interface

Yes

No

Yes

RS485

Overview

Interface not integrated; Retrofit RS485 interface card.

6-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Install the RS485 interface in the inverter

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Installing the RS485 interface
Procedure

► Install the RS485 interface in the inverter in accordance with the interface card installation instructions.

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made data cable (optional extra; not supplied)

or

self-made cable connection using RS485 data cable with RJ45 plug and terminal block connector

Caution

Risk of damage to the unit!
The Solar-Log™ also has an RJ45 socket, which must never be connected to the RJ45
socket on the inverter.

Only connect inverters via the RS485/422 Solar-Log™ interface(s).

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

► 7

► 2

► 1

► 2

► 2

► 3

► 3

► 3

► 4

5 - unused

6 - unused

► 4

► 8

3. Insert the RJ45 plug into any RJ45 socket on inverter 1.
4. Close the inverter if no other inverters are to be connected.
5. Insert the terminal block connector into the Solar-Log™ RS485 socket.