Vaillant

Vaillant – auroPOWER VPI /1 and VPI (RS485)

Connect the inverters to each other

Connect using a 2 wire, shielded data cable

Where to connect: Terminal strip inside the inverter

The RS485 connections on the terminal strip are each double connections so that the wiring can be con-

tinued to the next inverter.

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Connect terminal A on inverter 1 to terminal A on inverter 2.

3. Connect the other inverters to each other in the same way.

4. Terminate in the last inverter. In the inverter connect the free terminal A to terminal B using the

supplied 330

Ω terminating resistor.

Devices without a transformer: From unit generation VPI xx00 /2 the 330

Ω resistor is switched on

using the DIP switch. When the unit is delivered the terminal resistor is switched on.

5. Close inverters.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Setting:
Units without transformers: using the DIP switch inside the inverter
Units with transformers: using the inverter operating display.

Procedure: Start according to the inverter's instructions