54 omron, 54�1 omron – Solare Datensysteme Solar-Log User Manual

Page 159

Advertising
background image

159

Omron

Omron

54 Omron

54�1 Omron

Easy Installation

Termination

Addressing

Interface

No

Bridge 9 -> 10

Yes

RS485

Overview

Integrated interface

Where to connect: Terminal strip inside the inverter

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

The wiring is done using a

self-made, shielded 3 wire data cable and terminal block connector.

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Connect the cable as shown in the following diagram.

Solar-Log™ terminal strip connector

Inverter terminal strip

RS485/422 B

Terminal strip TB401

► 1

► Pin 4 - Data +

► 3

► Pin 3 - GND

► 4

► Pin 5 - Data -

3. If only one inverter is to be connected it must be terminated. To do this a bridge must be inserted on

the inverter between pins 9 and 10.

4. Close the inverter if no other inverters are to be connected.

5. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

The wiring is done using a

self-made, shielded 3 wire data cable and terminal block connector.