63 q3 – Solare Datensysteme Solar-Log User Manual

Page 181

Advertising
background image

181

Q3

Q3 (RS485)

63 Q3

63�1 Q3 (RS485)

Easy Installation

Termination

Addressing

Interface

No

Yes

Yes

RS485

Overview

Integrated interface

Where to connect: Between the COM round sockets on the outside of the inverter.

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Connect the inverters to each other

Allocate communication address

Connect inverters to the Solar-Log™

Connecting is done using a self-made, shielded 3 wire data cable and terminal block connector.

Procedure

1.

Connect wires as shown in the diagram below.

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► 1 (RS485-A)

► 3

► 3 (GND)

► 4

► 2 (RS485-B)

2. If only one inverter is to be connected terminate this in accordance with the inverter instructions.

3. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a self-made daisy chain cable.

Where to connect: X2 connection socket on outside of the inverter.

Procedure

1.

Insert the plug into socket X2 on inverter 1.

2. Insert the other end of the wire into the X2 socket on inverter 2.

3. Connect the other inverters to each other in the same way.

4. Terminate in the last inverter in accordance with the inverter instructions.