ALPHA-SOL

ALPHA-SOL

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► R+

► 1

► T+

► 4

► R-

► 4

► T-

4. If only one inverter is to be connected terminate this in accordance with the inverter instructions.

5. Close the inverter if no other inverters are to be connected.

6. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a 4 wire, shielded data cable

Where to connect: Terminal strip inside the inverter on the retrofitted RS485 interface card

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. Connect terminals R+, T+, R- and R+ of inverter 1 to the corresponding terminals on inverter 2.

3. Connect the other inverters to each other in the same way.

4. Terminate in the last inverter according to the inverter instructions.

5. Close inverters.