4�3 advanced energy - ae-tx – Solare Datensysteme Solar-Log User Manual

Page 29

Advertising
background image

29

Advanced Energy

Advanced Energy - AE-TX

4�3 Advanced Energy - AE-TX

Easy Installation

Termination

Addressing

Interface

No

Jumper

Yes

RS485

Select “PVPowered” during the inverter detection

Overview

Integrated interface

Where to connect: Modbus Slave socket on interface card

3-pin wiring

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™

Connect inverters to the Solar-Log™

Set the address of the inverters.

Connect the inverters to each other

Connect inverters to the Solar-Log™

The wiring is done using a

self-made 3 pin connection cable and terminal block connector.

Note

The transfer rate for Modbus (RS485) on delivery to the customer is set to 9600bps. Please
check these settings.

Procedure

1.

Open the inverter as shown in the inverter‘s instructions.

2. Pull the free wires through the wire opening in the inverter.

3. If you are making the cable yourself, connect the wires as shown in the following diagram

4. If only one inverter is to be connected this must be terminated.

Inside the inverter set the supplied jumper from „J4“ to „J5“.

5. Setting the address for the inverter: Set SW1 to „0“ and SW2 to „1“ in order to set the parameters for

the inverter with the address „01“.

6. Close the inverter if no other inverters are to be connected.

7. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Solar-Log™ terminal strip connector

RJ45 inverter

Terminal

PIN

► 1

2 - D+

► 3

1 - GND

► 4

3 - D-

Connect the inverters to each other

The wiring is done using a

self-made connection cable and terminal block connector.

Where to connect: Terminal strip inside the inverter