72�3 ipe sn series – Solare Datensysteme Solar-Log User Manual

Page 208

Advertising
background image

208

Schüco

IPE SN series

72�3 IPE SN series

Easy Installation

Termination

Addressing

Interface

Yes

Yes

Yes

RS485

Selectable under Sunways

Overview

Integrated interface.

Where to connect: Terminal strip inside the inverter.

-

750 V models: 4 RS485 terminals on 10 pin terminal strip.

-

850 V models: 4 pin RS485 terminal strip.

2-pin wiring.

Communication address must be allocated.

Installation steps

Switch off the inverters and Solar-Log™.

Connect inverters to the Solar-Log™.

Connect the inverters to each other.

Allocate communication address.

Connect inverters to the Solar-Log™

The wiring is done using a

ready-made Sunways data cable (optional extra; not supplied)

or

self-made, shielded 2 wire data cable and terminal block connector.

Procedure

1.

Open the inverter as shown in the inverter‘s instructions.

2. Pull the free wires through the wire opening in the inverter.

3. If you are making the cable yourself, connect the wires as shown in the following diagram:

Solar-Log™ terminal strip connector

Inverter terminal strip

Terminal

Terminal

► 1

► RS485+

► 4

► RS485-

4. If only one inverter is to be connected, terminate it according to the inverter instructions.

5. Close the inverter if no other inverters are to be connected.

6. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Connect the inverters to each other

Connect using a 2 wire, shielded data cable

Where to connect: Terminal strip inside the inverter

-

750 V models: 4 RS485 terminals on 10 pin terminal strip

-

850 V models: 4 pin RS485 terminal strip

The RS485 connections on the terminal strip are each double connections so that the wiring can be con-

tinued to the next inverter.