PrimeVOLT

PrimeVOLT

Procedure

1.

Open the inverter as shown in the inverter's instructions.

2. If you are making the cable yourself, connect the wires as shown in the following diagram:

Terminal strip inside the inverter

Terminal strip inside the inverter

RS485 terminal

RS485 terminal

► 1 T/R 1+

► 1 T/R 2+

► 2 T/R 1-

► 2 T/R 2-

3. Connect terminals A and B on inverter 1 to the corresponding terminals on inverter 2.

4. Connect the other inverters to each other in the same way.

5. Terminate in the last inverter.

Set the DIP switch for the terminal resistor to ON.

6. Close inverters.

7. Insert the terminal block connector into the Solar-Log™ RS485 socket.

Allocate communication address

Recommendation: Continuous numbering starting with 1.

Setting: Using the inverter DIP switch

Procedure: Start according to the inverter's instructions