Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
119
5
Motor control (MCTRL)
5.4
V/f characteristic control (VFCplus)
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.4.3
Optimising the control mode
The V/f characteristic control (VFCplus) is generally ready for operation. It can be adapted
subsequently by adapting the characteristic and/or the drive behaviour.
Adapting characteristic
For the linear and quadratic characteristic, it is also possible to match its curve to different load
profiles or motors by adapting the V/f base frequency (
) and the V
min
boost (
).
Adapting the V/f base frequency
Freely defining the characteristic
The V/f characteristic can also be defined freely if the linear and quadratic characteristics are not
suitable.
Defining a user-defined V/f characteristic
Adapting drive behaviour
• Limitation of the maximum current by a current limitation controller (e.g. to prevent the motor
from stalling or to limit to the maximally permissible motor current).
• Adaptation of the field frequency by a load-dependent slip compensation (improved speed
accuracy for systems without feedback)
• Adaptation of the controller parameters of the slip regulator if V/f control (VFCplus + encoder)
is selected.
Parameterising the slip regulator