C00572 | brake resistor overload threshold, C00574 | resp. to brake resist. overtemp, C00579 | resp. to max. speed/output freq. reached – Lenze E84DSxxx User Manual

Page 563: C00572, C00574, Old set in, Tting of, C00579, 15 parameter reference

Advertising
background image

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

563

15

Parameter reference

15.2

Parameter list | C00572

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00572

C00574

C00579

Parameter | Name:

C00572 | Brake resistor overload threshold

Data type: UNSIGNED_8

Index: 24003

d

= 5DC3

h

Adjustable threshold for monitoring the brake resistor utilisation

• The response for reaching the threshold can be selected in

C00574

.

Setting range

(min. value | unit | max. value)

Lenze setting

0

%

100 100 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00574 | Resp. to brake resist. overtemp.

Data type: UNSIGNED_8

Index: 24001

d

= 5DC1

h

Response which is triggered if the threshold set in

C00572

for monitoring brake resistor utilisation is reached.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00579 | Resp. to max. speed/output freq. reached

Data type: UNSIGNED_8

Index: 23996

d

= 5DBC

h

Response when the max. speed limit (

C00909

) or output frequency limit (

C00910

) has been reached.

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Advertising