1 signal interpolation, Signal interpolation, 17 function library – Lenze E84DSxxx User Manual
Page 737

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
737
17
Function library
17.1
Function blocks | L_Interpolator_1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter
17.1.18.1 Signal interpolation
If signal interpolation is active (
= 1)
, the output signal will not reach the level of the corresponding
input signal until all interpolation steps parameterised in
have been performed:
[17-10] Signal characteristic
Parameter
Possible settings
Info
Signal interpolation of the dnPhIn_p
and nNIn_a input signals
• Lenze setting: Off
0 Off
1 On
Signal monitoring of the dnPhIn_p
input signal
• Lenze setting: Off
0 Off
1 On
1
65535 Number of interpolation steps
• Corresponds to the receive cycle
of the data telegrams in [ms].
• Lenze setting: 1
0
65535 Limit value for missing data
telegrams
• Lenze setting: 5
0
0 Filters
In preparation!
Setpoint signal
Interpolated setpoint signal
Receive cycle in [ms] = Number of interpolation steps (in our example: 5)
10
5
15
t
ms
Dy from cycle 1
Dy from cycle 2
signal
cycle 1
cycle 2
cycle 3