C00953 | l_interpolator_1: filter, C00966 | vfc: time const. slip comp, 15 parameter reference – Lenze E84DSxxx User Manual

Page 619

Advertising
background image

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

619

15

Parameter reference

15.2

Parameter list | C00952

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00952

C00953

C00966

Parameter | Name:

C00952 | L_Interpolator_1: Limit value - error cycles

Data type: UNSIGNED_16

Index: 23623

d

= 5C47

h

The

L_Interpolator_1

FB: Limit value for missing data telegrams

Setting range

(min. value | unit | max. value)

Lenze setting

0

65535 5

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00953 | L_Interpolator_1: Filter

Data type: UNSIGNED_8

Index: 23622

d

= 5C46

h

From version 02.00.00

FB

L_Interpolator_1

: Filter

Setting range

(min. value | unit | max. value)

Lenze setting

0

5 0

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00966 | VFC: Time const. slip comp.

Data type: UNSIGNED_16

Index: 23609

d

= 5C39

h

Filter time constant of the slip compensation for V/f characteristic control (

VFCplus

)

• The time constant of slip compensation serves to specify the dynamics of slip compensation for V/f characteristic

control without feedback.

• The lower the selected time constant, the higher the dynamic performance of the slip compensation.

Setting range

(min. value | unit | max. value)

Lenze setting

1

ms

6000 100 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1