7 parameterisable additional functions, 1 selection of the switching frequency, Parameterisable additional functions – Lenze E84DSxxx User Manual

Page 149: Selection of the switching frequency, 5motor control (mctrl), Stop

Advertising
background image

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

149

5

Motor control (MCTRL)

5.7

Parameterisable additional functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.7

Parameterisable additional functions

5.7.1

Selection of the switching frequency

The switching frequency of the inverter that can be selected in

C00018

influences the smooth

running performance and the noise generation in the connected motor as well as the power losses

in the controller.
The lower the switching frequency the higher the concentricity factor, the smaller the losses, and

the higher the noise generation.

Settable switching frequencies

Tip!
The Lenze setting

C00018

= 2 (8 kHz var./drive-opt.) is the optimal value for standard

applications.

Stop!

If operated at a switching frequency of 16 kHz, the output current of the controller must

not exceed the current limit values specified in the technical data!

Defining current and speed limits

( 111)

Note!

• Operate mid-frequency motors only at a switching frequency of 8 kHz or 16 kHz

(var./drive-opt.).

• If operated at a switching frequency of 16 kHz, the Ixt evaluation (

C00064

) is

considered including the required derating to 67 % of the rated device current at

switching frequencies of 2.4 and 8 kHz.

Selection in

C00018

1 4 kHz var./drive-optimised

21 8 kHz var./drive-opt./4 kHz min

2 8 kHz var./drive-optimised

22 16 kHz var./drive-opt./4 kHz min

3 16 kHz var./drive-optimised

23 16 kHz var./drive-opt./8 kHz min

5 2 kHz constant/drive-optimised

31 8 kHz var./min. Pv/4 kHz min

6 4 kHz constant/drive-optimised

32 16 kHz var./min. Pv/4 kHz min

7 8 kHz constant/drive-optimised

33 16 kHz var./min. Pv/8 kHz min

8 16 kHz constant/drive-optimised

Abbreviations used:

• "var.": Adaptation of the switching frequency

depending on the current

• "drive-opt.": drive-optimised modulation ("sine/delta

modulation")

• "fixed": fixed switching frequencies

• "min. Pv": additional reduction of power loss

11 4 kHz var./min. Pv
12 8 kHz var./min. Pv
13 16 kHz var./min. Pv
15 2 kHz constant/min. Pv
16 4 kHz constant/min. Pv
17 8 kHz constant/min. Pv
18 16 kHz constant/min. Pv