Parameter reference

15.2

Parameter list | C02607

636

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02607

C02610

Parameter | Name:

C02607 | Holding brake: Status

Data type: UNSIGNED_16

Index: 21968

d

= 55D0

h

Switching status of the holding brake control

Holding brake control

Display area

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Info

Bit 0 Brake applied

Holding brake is completely applied

Bit 1 Brake released

Holding brake is completely released

Bit 2 Feedforward control active

Feedforward control for holding of the load via the motor

is active before the holding brake releases.

Bit 3 Closing active

The brake closing time (

C02589/1

) expires

Bit 4 Forced release active

In case of automatic operation of the holding brake

control, the brake is directly released via the MCK input

bBrkRelease = TRUE

Bit 5 Release active

The brake release time (

C02589/2

) expires

Bit 6 Setpoint synchronisation active

A speed setpoint at the MCK is approached along a

defined ramp after brake release

Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved

Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C02610 | MCK: Accel./decel. times

Data type: UNSIGNED_32

Index: 21965

d

= 55CD

h

Ramp times for speed setpoint synchronisation
Setting range

(min. value | unit | max. value)

0.000

s

999.999

Subcodes

Lenze setting

Info

C02610/1

2.000 s

MCK: Holding brake ramp time synchr.

• Ramp time for approaching the speed setpoint at the

MCK after holding brake release.

Holding brake control

C02610/2

2.000 s

MCK: Ramp time synchr. setpoint

• Time for synchronisation ramps between setpoint

jumps occurring through the exceedance of

minimum and maximum speed setpoint limit ranges.

C02610/3

2.000 s

MCK: SM stopping ramp

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000