OT1: Maximum torque reached [xx.0123.00001]

OC7: Motor overcurrent [xx.0123.00007]

OU: DC bus overvoltage [xx.0123.00014]

LU: DC bus undervoltage [xx.0123.00015]

Response (Lenze setting printed in bold)

Setting:

C00608

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device indicates that the maximally possible torque

at the motor shaft has been reached.

C00057

displays the current torque.

Reduce motor load.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Maximum current monitoring has tripped.

Check and, if required, correct dimensioning of the load

with regard to the installed device power.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected an overvoltage in the DC bus. To

protect the device hardware, the inverter control is

switched off.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• If this error message remains active longer than the

time set in

C00601

, a "Fault" is tripped.

• Reduce load in generator mode.

• Use a brake resistor.

• Use a regenerative power supply unit.

• Establish a DC-bus connection.

Response (Lenze setting printed in bold)

Setting:

C00600/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected a DC bus undervoltage. The

inverter control is switched off because the drive

properties of the motor control cannot be provided

anymore due to the DC bus undervoltage.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• Switch on mains supply or ensure sufficient supply via

DC bus.

• Adjust setting in

C00142

if required.