355

9

Diagnostics & error management

9.10

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

9.10.6

Cause & possible remedies

This chapter contains all error messages of the controller operating system in numerical order of the

error numbers. The list provides detailed information on the response to the error message as well

as information on the cause & possible remedies.

Tip!
A list of all error messages of the controller operating system in alphabetical order can be

found in the previous chapter "

Short overview (A-Z)

"

( 353)

.

Su02: One mains phase is missing [xx.0111.00002]

Su03: Too frequent mains switching [xx.0111.00003]

Su04: CU insufficiently supplied [xx.0111.00004]

Note!

For the sake of legibility, the

Logbook

and

C00165

display the error number with the

following syntax:

[Error type].[Error subject area no.].[Error ID]
In this documentation, "xx", a wildcard, stands for the error type since it is configurable

for many error messages.

Response (Lenze setting printed in bold)

Setting:

C00565

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

One mains phase of a three-phase supply has failed.

Check mains connection (plug X10).

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Too frequent mains switching of the power section.

• The device recognises if the power section is switched

on and off too frequently.

• To protect internal charging connections from

destruction, the device reports this error and prevents

the controller inhibit. All other functions are active.

The error must be acknowledged.

The minimum waiting time between two mains

switching processes is approximately three seconds.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

After switching on the device, the 24V supply voltage for

the control electronics is too low (100 ms after switch-on

U is < 19V).

With internal supply voltage via the power electronics,

the controller must be replaced.

With external supply voltage, check the correct

connection and/or the stability of the supply voltage.