C00760

Parameter | Name:

C00760 | LA_SwitchPos: Analog connection list

Data type: UNSIGNED_16

Index: 23815

d

= 5D07

h

Connection parameters for "Switch-off positioning" application: 16-bi inputs

• Selection of the 16 bit output signals to be connected to the 16 bit input signals

• The selection list contains all 16 bit output signals which can be assigned to the 16 bit inputs displayed by the

subcodes.

Selection list
See

selection list - analog signals

Subcodes

Lenze setting

Info

C00760/1

0: Not connected

LA_SwitchPos

: wCANDriveControl

(input for control word from CAN to device control)

C00760/2

0: Not connected

LA_SwitchPos

: wMCIDriveControl

(input for control word from communication interface to

device control)

C00760/3

0: Not connected

LA_SwitchPos

: nVoltageAdd_a

(input for additive voltage impression)

C00760/4

0: Not connected

LA_SwitchPos

: nBoost_a

(input for additional setpoint for the motor voltage at

speed = 0)

C00760/5

0: Not connected

LA_SwitchPos

: nPWMAngleOffset

(input for additional offset for the electrical angle of

rotation)

C00760/6

0: Not connected

LA_SwitchPos

: nTorqueMotLim_a

(input for maximum torque in motor mode)

C00760/7

0: Not connected

LA_SwitchPos

: nTorqueGenLim_a

(input for maximum torque in generator mode)

C00760/8

0: Not connected

LA_SwitchPos

: nMainSetValue_a

(input for main speed setpoint)

C00760/9

0: Not connected

LA_SwitchPos

: nAuxSetValue_a

(input for additional speed setpoint)

C00760/10

0: Not connected

LA_SwitchPos

: nGPAnalogSwitchIn1_a

(input for analog-value selector analog signal 1)

C00760/11

0: Not connected

LA_SwitchPos

: nGPAnalogSwitchIn2_a

(input for analog-value selector analog signal 2)

C00760/12

0: Not connected

LA_SwitchPos

: nGPArithmetikIn1_a

(input for arithmetic function analog signal 1)

C00760/13

0: Not connected

LA_SwitchPos

: nGPArithmetikIn2_a

(input for arithmetic function analog signal 2)

C00760/14

0: Not connected

LA_SwitchPos

: nGPMulDivIn_a

(input for analog signal for multiplication/division)

C00760/15

0: Not connected

LA_SwitchPos

: nGPCompareIn1_a

(input for comparison operation analog signal 1)

C00760/16

0: Not connected

LA_SwitchPos

: nGPCompareIn2_a

(input for comparison operation analog signal 2)

C00760/17

0: Not connected

LA_SwitchPos

: wSMCtrl

(interface to optional safety system)

C00760/18

0: Not connected

Reserved

C00760/19

0: Not connected

Reserved

C00760/20

0: Not connected

Reserved

C00760/21

0: Not connected

Reserved