Diagnostics & error management

9.10

Error messages of the operating system

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

OC14: Direct-axis current controller limitation [xx.0123.00096]

OC15: Cross current controller limitation [xx.0123.00097]

OC16: Torque controller limitation [xx.0123.00098]

FC1: Field controller limitation [xx.0123.00099]

OC6: I2xt overload - motor [xx.0123.00105]

Response (Lenze setting printed in bold)

Setting:

C00570/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Direct-axis current controller limitation is active.

• Observe load requirements.

• Correct dimensioning or reduce setpoint generation

dynamics if necessary.

Motor control

Response (Lenze setting printed in bold)

Setting:

C00570/2

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Cross current controller limitation is active.

• Observe load requirements.

• Correct dimensioning or reduce setpoint generation

dynamics if necessary.

• Check parameter setting of the current controller

with regard to the motor controllers (e.g. reduce Vp).

Motor control

Response (Lenze setting printed in bold)

Setting:

C00570/3

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Actuator limitation according to speed controller.

• Observe load requirements.

• Correct dimensioning or reduce setpoint generation

dynamics if necessary.

Motor control

Response (Lenze setting printed in bold)

Setting:

C00570/4

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The output of the field controller has reached its

maximum limit value. The drive is at the torque limit in

the field weakening range.

• Observe load requirements.

• Correct dimensioning or reduce setpoint from the

field weakening range if necessary.

Motor control

Response (Lenze setting printed in bold)

Setting:

C00606

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Thermal overload of the motor.

• Observe load requirements.

• Correct dimensioning if necessary.

• In case of VFCplus operation: Check Vmin boost

(

C00016

).

Set

Vmin boost