C00064 | device utilisation (ixt), C00066 | thermal motor load (i·xt), C00070 | vp speed controller – Lenze E84DSxxx User Manual
Page 487: C00071 | ti speed controller, C00066, C00070, C00071, C00071/1, C00070/1, The gain vp

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
487
15
Parameter reference
15.2
Parameter list | C00064
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00064
C00066
C00070
C00071
Parameter | Name:
C00064 | Device utilisation (Ixt)
Data type: INTEGER_16
Index: 24511
d
= 5FBF
h
Display of the device utilisation Ixt in different time resolutions
• If the value displayed here exceeds the threshold set in
, the error message "OC5: Device overload (Ixt)"
is output and the "Fault" error response is returned.
Display range
(min. value | unit | max. value)
0.00
%
250.00
Subcodes
Info
C00064/1
Device utilisation (Ixt)
• Maximum value of the pulse utilisation (C00064/2)
and permanent utilisation (C00064/3).
C00064/2
Device utilisation (Ixt) 15s
• Pulse utilisation over the last 15 seconds (only for
loads >160 %).
C00064/3
Device utilisation (Ixt) 3 min
• Permanent utilisation over the last 3 minutes.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00066 | Thermal motor load (I²xt)
Data type: INTEGER_16
Index: 24509
d
= 5FBD
h
Display of the thermal motor load, sensorlessly determined using a motor model
• If the value displayed here exceeds the threshold set in
, the fault message "OC6: Thermal motor overload
(I2xt)" is output and the fault response set in
is executed (default setting: "Warning").
Display range
(min. value | unit | max. value)
0.00
%
199.99
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00070 | Vp speed controller
Data type: UNSIGNED_16
Index: 24505
d
= 5FB9
h
Amplification factor Vp of the speed controller for different motor control modes
Setting range
(min. value | unit | max. value)
0.00
600.00
Subcodes
Lenze setting
Info
C00070/1
15.00
: Vp speed controller
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00071 | Ti speed controller
Data type: UNSIGNED_16
Index: 24504
d
= 5FB8
h
Reset time Ti of the speed controller for different motor control modes
Setting range
(min. value | unit | max. value)
0.0
ms
6000.0
Subcodes
Lenze setting
Info
C00071/1
100.0 ms
: Ti speed controller
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10