9diagnostics & error management – Lenze E84DSxxx User Manual

Page 354

Advertising
background image

9

Diagnostics & error management

9.10

Error messages of the operating system

354

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

xx.0125.00011

0x190b

6411

Io11: DigOut level

Warning

C00598/3

0xF000

xx.0123.00145

0x1791

6033

LP1: Motor phase failure

No Reaction

C00597

0x3000

xx.0123.00015

0x170f

5903

LU: DC bus undervoltage

Trouble

C00600/1

0x3100

xx.0140.00013

0x280d

10253

MCI1: Module missing / incompatible

No Reaction

C01501/2

0x7000

xx.0123.00016

0x1710

5904

OC1: Power section - short circuit

Fault

-

0x2000

xx.0123.00017

0x1711

5905

OC2: Power section - earth fault

Fault

-

0x2000

xx.0119.00050

0x1332

4914

OC5: Ixt overload

Fault

-

0x2000

xx.0123.00105

0x1769

5993

OC6: I2xt motor overload

Warning

C00606

0x2000

xx.0123.00007

0x1707

5895

OC7: Motor overcurrent

Fault

-

0x2000

xx.0123.00030

0x171e

5918

OC10: Max. current reached

Fault

-

0x2000

xx.0123.00071

0x1747

5959

OC11: Active clamp operation

Warning

-

0xF000

xx.0123.00065

0x1741

5953

OC12: I2xt overload - brake resistor

Fault

-

0xF000

xx.0123.00090

0x175a

5978

OC13: Max. current for Fch exceeded

Fault

-

0xF000

xx.0123.00096

0x1760

5984

OC14: Direct-axis current controller limitation

No Reaction

C00570/1

0xF000

xx.0123.00097

0x1761

5985

OC15: Cross current controller limitation

No Reaction

C00570/2

0xF000

xx.0123.00098

0x1762

5986

OC16: Torque controller limitation

No Reaction

C00570/3

0xF000

xx.0123.00031

0x171f

5919

OC17: Clamp sets pulse inhibit

No Reaction

C00569/1

0xF000

xx.0119.00001

0x1301

4865

OH1: Heatsink overtemperature

Fault

-

0x4000

xx.0119.00015

0x130f

4879

OH3: Motor temperature (X21) triggered

Fault

C00585

0x4000

xx.0119.00000

0x1300

4864

OH4: Heatsink temp. > shutdown temp. -5°C

No Reaction

C00582

0x4000

xx.0123.00032

0x1720

5920

OS1: Max. speed limit reached

No Reaction

C00579

0x8400

xx.0123.00001

0x1701

5889

OT1: Max. torque reached

No Reaction

C00608

0x8300

xx.0123.00093

0x175d

5981

OT2: Speed controller output limited

No Reaction

C00567

0xF000

xx.0123.00014

0x170e

5902

OU: Überspannung Zwischenkreis

Trouble

-

0x3100

xx.0144.00001

0x2c01

11265

PS01: No memory module

Warning

-

0x6300

xx.0144.00002

0x2c02

11266

PS02: Invalid par. set

Fault

-

0x6300

xx.0144.00003

0x2c03

11267

PS03: Invalid device par. set

Fault

-

0x6300

xx.0144.00004

0x2c04

11268

PS04: Invalid MCI par. set

Fault

-

0x6300

xx.0144.00007

0x2c07

11271

PS07: Invalid memory module par. set

Fault

-

0x6300

xx.0144.00008

0x2c08

11272

PS08: Invalid device par.

Fault

-

0x6300

xx.0144.00009

0x2c09

11273

PS09: Invalid par. format

Fault

-

0x6300

xx.0144.00010

0x2c0a

11274

PS10: Memory module binding invalid

Fault

-

xx.0123.00205

0x17cd

6093

SD3: Open circuit - feedback system

Fault

C00586

0x7300

xx.0123.00200

0x17c8

6088

SD10: Speed limit - feedback system 12

Fault

C00607

0x7300

xx.0111.00002

0x0b02

2818

Su02: One mains phase is missing

Warning

C00565

0x3000

xx.0111.00003

0x0b03

2819

Su03: Too frequent mains switching

Fault

-

0x3000

xx.0111.00004

0x0b04

2820

Su04: CU Insufficiently Supplied

Warning

-

0x3000

xx.0111.00005

0x0b05

2821

Su05: IO supply overload

Warning

C00598/4

0x3000

xx.0980.00001

-

-

US01: User error 1

No Reaction

C00581/1

0x6200

xx.0981.00002

-

-

US02: User error 2

No Reaction

C00581/2

0x6200

xx.0982.00003

-

-

US03: User error 3

No Reaction

C00581/3

0x6200

xx.0983.00004

-

-

US04: User error 4

No Reaction

C00581/4

0x6200

Error number

Error message

Response

(Lenze setting)

can be set in

CAN Emergency

Error Code

32 bits

16 bits

hex

16 bits

dec

Advertising