OC1: Power section - short circuit [xx.0123.00016]

OC2: Power section - earth fault [xx.0123.00017]

OC10: Maximum current reached [xx.0123.00030]

OC17: Clamp sets pulse inhibit [xx.0123.00031]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised a short circuit of the motor

phases. To protect the device electronics, the inverter

control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If the device is inappropriately dimensioned with

regard to the motor load and the current limitation in

the controller (Imax controller) is set incorrectly, this

error message may also occur.

Motor control: Defining current limits

• Check motor connections and the corresponding plug

connector on the device.

• Only use permissible combinations of device power

and motor power.

• Do not set the dynamics of the current limitation

controller too high.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised an earth fault at one of the

motor phases. To protect the device electronics, the

inverter control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If motor filter, motor cable length, and cable type

(shielding capacity) are dimensioned incorrectly, this

error message may occur due to leakage currents to

PE.

• If motor filters with additional terminals for +UG and

–UG and devices greater or equal 3 kW are used, the

earth fault detection may be triggered due to leakage

currents to +UG and –UG.

• A cause can also be the use of shielded motor cables

longer than 50 m.

• Check motor connections and the corresponding plug

connector on the device.

• Use motor filters, cable lengths, and cable types

recommended by Lenze.

• If motor filters with additional terminals for +UG and

–UG and devices greater or equal 3 kW are used:

Up to version 01.xx.xx:

Set resp. to earth fault

(

C00602

) to "0: No Reaction".

From version 02.00.00:

Deactivate earth fault

detection during operation by setting the filter

time (

C01770

) to 250 ms.

• If motor cables longer than 50 m are used:

From version 02.00.00:

Increase filter time for earth

fault detection during operation (

C01770

).

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device displays that the maximum current has been

reached.

• Check and, if required, correct dimensioning of the

load with regard to the installed device power.

• Check the maximum current settings in

C00022

(Imax in motor mode) and

C00023

(Imax in generator

mode).

Response (Lenze setting printed in bold)

Setting:

C00569/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

Due to a short overcurrent, the inverter was switched off

for a short time (clamp disconnection).

• Check and, if required, correct dimensioning of the

load with regard to the installed device power.

• Reduce the dynamics of the setpoint change or speed

control.