Os1: maximum speed limit reached [xx.0123.00032, Id3: cinh motor data identification [xx.0123.00058, Oc12 – Lenze E84DSxxx User Manual
Page 359: Oc12: i2xt brake resistor overload, Error m, Oc12: i2xt overload brake resistor, Xx.0123.00057, Xx.0123.00058, Xx.0123.00059, Xx.0123.00065

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
359
9
Diagnostics & error management
9.10
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
OS1: Maximum speed limit reached [xx.0123.00032]
ID1: Motor data identification error [xx.0123.00057]
ID3: CINH motor data identification [xx.0123.00058]
ID4: Resistance identification error [xx.0123.00059]
OC12: I2xt overload - brake resistor [xx.0123.00065]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised that the maximum speed has
been reached.
• Limit setpoint selection to maximum values.
• Adjust set speed limitation (
) and frequency
limitation (
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
During the identification of motor parameters, an error
has occurred.
Possible causes:
• Interrupted motor cable.
• Switched-off power section during the identification.
• Implausible start parameter settings.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Correct start parameters for the motor parameter
identification (motor nameplate data).
• Stable power supply of the device.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has detected controller inhibit during the
motor data identification.
• This cancels the identification process. The Lenze
setting of the motor data is used.
• Do not set controller inhibit during the motor data
identification.
• Do not execute any device function which may
activate controller inhibit.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised that an error has occurred in
the calculation of the motor cable resistance.
• The parameters for cable cross-section and cable
length are implausible.
Enter sensible values for cable cross-section and motor
cable length.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Too frequent and too long braking processes.
Check drive dimensioning.