C00594 | resp. to control word error, C00597 | resp. to motor phase failure, C00598 | resp. to i/o monitoring – Lenze E84DSxxx User Manual
Page 567: C00597, Will take place, C00598, C00598/1, C00594/2, C00598/3, C00598/4

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
567
15
Parameter reference
15.2
Parameter list | C00594
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00594
C00597
C00598
Parameter | Name:
C00594 | Resp. to control word error
Data type: UNSIGNED_8
Index: 23981
d
= 5DAD
h
Configuration of device control monitoring
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
5 Warning
Subcodes
Lenze setting
Info
C00594/1
1: Fault
Response if error bit 14 in the CAN control word is set.
C00594/2
1: Fault
Response if error bit 14 in the MCI control word is set.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00597 | Resp. to motor phase failure
Data type: UNSIGNED_8
Index: 23978
d
= 5DAA
h
Response to motor phase failure
• If a phase current does not exceed the threshold set in
for more than one period, the response set here
will be triggered.
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00598 | Resp. to I/O monitoring
Data type: UNSIGNED_8
Index: 23977
d
= 5DA9
h
Configuration of analog input monitoring
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
5 Warning
Subcodes
Lenze setting
Info
C00598/1
3: TroubleQuickStop
Response to open circuit at AIN1 if configured as
4 ... 20 mA current loop
C00598/2
0: No Reaction
Reserved
C00598/3
5: Warning
Resp. to digital output level
C00598/4
5: Warning
Resp. to IO supply overload
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1