C00599

C00600

C00601

C00602

Parameter | Name:

C00599 | Motor phase failure threshold

Data type: INTEGER_16

Index: 23976

d

= 5DA8

h

Threshold for motor phase failure monitoring

• 100 % ≡ rated inverter current (

C00098

)

• If a phase current does not exceed the threshold set here for more than one period, the response to motor phase

failure set in

C00597

will be triggered.

Setting range

(min. value | unit | max. value)

Lenze setting

1.00

%

100.00 5.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00600 | Resp. to DC bus voltage

Data type: UNSIGNED_8

Index: 23975

d

= 5DA7

h

Configuration of monitoring of the motor control (group 3)
Selection list

1 Fault
2 Trouble

Subcodes

Lenze setting

Info

C00600/1

2: Trouble

Response to DC bus undervoltage

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00601 | Del. resp. to fault: DC bus overvoltage

Data type: UNSIGNED_16

Index: 23974

d

= 5DA6

h

Error response delay times
Setting range

(min. value | unit | max. value)

0.000

s

65.000

Subcodes

Lenze setting

Info

C00601/1

2.000 s

Delay time for triggering the "DC-bus overvoltage" error

• If a DC-bus overvoltage occurs, an error will not be

triggered until the set delay time has elapsed.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00602 | Resp. to earth fault

Data type: UNSIGNED_8

Index: 23973

d

= 5DA5

h

Response to earth fault in the motor phase(s)
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1