Lowering the switching frequency due to high heatsink temperatures
Exceeding the maximally permissible heatsink temperature would lead to an inhibited drive due to

the "Overtemperature" error and a torquelessly coasting motor. Therefore, if the Lenze setting is

selected, the switching frequency is reduced to the next frequency below when the heatsink

temperature has risen to 5 °C below the maximally permissible temperature. After the heatsink has

cooled down, the controller automatically switches to the next frequency above until the set

switching frequency is reached.
Switching frequency reduction due to high heatsink temperature can be deactivated via

C00144

. If

the switching frequency reduction is deactivated, the "OH1: Heatsink overtemperature" error

message will be issued when the maximally permissible heatsink temperature is reached. An "Error"

response is the result and the motor is coasting.

Lowering of the switching frequency depending on the output current
"Variable" switching frequencies can be selected for the controller in

C00018

, where the controller

automatically lowers the switching frequency depending on the controller output current. The

modulation mode will not be changed.

When a "fixed" switching frequency is selected, no switching frequency changeover takes place. In

case of fixed frequencies, the controller output current is limited to the permissible value of the

corresponding switching frequency. In case of larger load impulses, the overcurrent interruption

may be activated, to which the controller responds with "Error".

Parameter

Info

Lenze setting

C00144

Switching frequency reduction (temp.)

1: On

The switching thresholds are given in the rated data in the 8400 protec hardware

manual.