9 braking operation/brake energy management, Braking operation/brake energy management, 5motor control (mctrl) – Lenze E84DSxxx User Manual

Page 170

Advertising
background image

5

Motor control (MCTRL)

5.9

Braking operation/brake energy management

170

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.9

Braking operation/brake energy management

When electric motors are braked, the kinetic energy of the drive train is fed back into the DC circuit

regeneratively. This energy leads to an increase in the DC bus voltage. In order to avoid overvoltage

in the DC bus, several different strategies can be used:

• Use of a brake resistor
• Stopping of the ramp function generator if brake chopper threshold exceeded (RFG_Stop)
• Use of the "inverter motor brake" function
• Combination of the above named options

In the case of inverters with a 3-phase supply, the following is also possible:

• Coupling of the inverters in a DC-bus connection
• Recovery of regenerative energy with a regenerative module

Tip!
In

C00175

, a ramp function generator stop (FB

L_NSet_1

) can be set for instances when the

brake resistor is controlled. This prevents overvoltage deactivation in the case of short

deceleration times.

Selecting the response to an increase of the DC-bus voltage

( 173)

Stop!

If the connected brake resistor is smaller than required, the brake chopper can be

destroyed!
Appropriate protective measures are described in subchapter "

Avoiding thermal

overload of the brake resistor

".

( 178)

Note!

• We recommend to use the brake chopper (brake transistor) which is integrated into

the controller for the braking operation, regardless of the selected motor mode.

• Connect the required brake resistor to the R

B1

and R

B2

terminals of the controller.

• For a DC-bus connection with other devices, we recommend to connect the

regenerative power supply module to terminals +UG and –UG.

• If none of these measures is taken, e.g. the overvoltage deactivation ("OU") may

respond in case of low deceleration times during regenerative operation.

Error

messages of the operating system

( 347)

To install the regenerative module, follow the instructions in the 8400 hardware

manual.

• The hardware manual has been stored in electronic form on the data carrier supplied

with the 8400 drive controller.

Advertising