6

I/O terminals

6.2

Analog terminals

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

6.2.1.1

Signal adaptation by means of characteristic

This function extension is available from version 02.00.00!

According to the illustration below, an individual characteristic can be parameterised via the

subcodes of

C00010

to provide different slopes and a dead band. Here, the input signal corresponds

to the X axis and the output signal corresponds to the Y axis:

[6-4]

Characteristic for analog inputs

In the »Engineer«, there is a parameterising dialog for entering the characteristic. This dialog also

displays the set characteristic graphically.

199.99 %

Œ

“



Ž





‘

’

y

max

-y

max

-x

max

x

max

y

min

-y

min

199.99 %

-199.99 %

-199.99 %

Parameter

Info

Lenze setting

Value Unit

C00010/1

AIN1: (+y0) = min

0.00 %

C00010/2

AIN1: (+x0) = Dead band

1.00 %

C00010/3

AIN1: (-y0) = (-min)

0.00 %

C00010/4

AIN1: (-x0) = (-Dead band)

1.00 %

C00010/5

AIN1: (+ymax)

199.99 %

C00010/6

AIN1: (+xmax)

199.99 %

C00010/7

AIN1: (-ymax)

199.99 %

C00010/8

AIN1: (-xmax)

199.99 %