Introduction: Parameterising the controller
2.4
Device access protection
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Activate device personalisation
The device personalisation is activated by setting a binding ID.
How to set the binding ID:
1. Enter the desired binding ID in
• The binding ID may have a maximum length of 16 characters.
• The following characters are permitted for the binding ID:
Small letters (a - z), capital letters (A - Z), digits (0 - 9)
2. Execute "Set binding ID" device command
= "1: On / start"
• After successful execution, status ON is displayed in
Deactivate device personalisation/change binding ID
The device personalisation is simply deactivated by deleting the set binding ID. If you want to
change the set binding ID, first delete the set binding ID as well. Then set the new binding ID.
How to delete the binding ID:
1. Enter the set binding ID in
.
• If controller and memory module do not have the same binding ID, enter the binding ID
of the memory module to delete the binding ID of both components.
2. Execute "Delete binding ID" device command
• After a successful deletion, status OFF is displayed in
Set binding ID
Activate device personalisation
0: Off / ready
Delete binding ID
Deactivate device personalisation/change binding ID
0: Off / ready
Status displays
Status of the last device command
-
Password protection - all communication channels
• Bit coded display of the active protective functions:
-
Bit 0 Only access to user menu
Bit 1 Parameter write protection
Bit 2 Parameter read protection
Bit 3 ... 14 Reserved
Bit 16 Memory module binding on
Parameter
Info
Lenze setting
Highlighted in grey = display parameter