5.10.1

Device overload monitoring (Ixt)

C00064/1...3

displays the device utilisation (ixt) in [%] in different time intervals:

• If the device utilisation reaches the switch-off threshold set in

C00123

:

• the "Fault" error response is returned.
• The "

OC5: Ixt overload

" error message will be entered into the Logbook.

• The bMctrlIxtOverload status output of the

LS_DeviceMonitor

system block will be set to

TRUE.

Parameter

Info

C00064/1

Device utilisation (Ixt)

• Maximum value of pulse utilisation (

C00064/2

)

and permanent utilisation (

C00064/3

).

C00064/2

Device utilisation (Ixt) 15s

• Pulse utilisation over the last 15 seconds (only for loads >160 %).

C00064/3

Device utilisation (Ixt) 3 min

• Permanent utilisation over the last 3 minutes.

Highlighted in grey = display parameter