[5-19] Tripping characteristic of the I

2

xt monitoring

Example:

C00120

= I

r

/I

N

x 100 %

C00054

= 150 % rated motor current

• After approx. 60 seconds,

C00066

has reached the final value (100 %) at output frequencies

f > 40 Hz.

• The controller outputs the "

OC6: I2xt overload motor

" error message and triggers the response

set in

C00606

(default setting: "Warning").

Tip!

• If forced ventilated motors are used, a premature response of the overload threshold can

be avoided by deactivating this function if necessary (

C00606

= "0: No Reaction").

• The current limits set in

C00022

and

C00023

influence the I

2

xt calculation only in an

indirect way. However, the operation of the motor at maximum possible load can be

averted.

Defining current and speed limits

( 111)

f: Output frequency

t: Release time

I

N

: Rated current of drive controller at a switching frequency of f = 8 kHz

I

r

: Rated motor current (see nameplate of motor)

C00054

: Apparent motor current

C00120

: Motor overload setting

60

180

240

300

360

t [s]

0.5

0

0

1.0

1.5

2.0

C00054

I

r

120

f = 0 Hz

f = 20 Hz

f > 40 Hz

I x 100 %

I

r

N

C00120 <

I x 100 %

I

r

N

C00120 =

I x 100 %

I

r

N

C00120 >