Diagnostics & error management
9.10
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS10: Memory module binding invalid [xx.0144.00010]
dF14: SW-HW invalid [xx.0145.00014]
dF18: BU RCOM error [xx.0145.00024]
dF25: CU RCOM error [xx.0145.00025]
dF21: BU watchdog [xx.0145.00033]
dF22: CU watchdog [xx.0145.00034]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device personalisation is active: The binding ID of the
memory module does not comply with the binding ID of
the controller.
• Use memory module/controller with matching
binding IDs.
• Contact machine manufacturer.
Note:
It is not possible for Lenze to modify a replacement
device via special accesses in such a way that it
cooperates with a personalised memory module.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Mains switching too frequent.
• Cyclic mains switching every 3 min is permissible.
• After switching the mains 3 times in one minute,
there must be a switching pause of 9 min.
• Please contact Lenze if the problem occurs again.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device error
Consultation with Lenze required.