Motor control (MCTRL)

5.10

Monitoring

188

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.10.8

Maximum torque monitoring

If the maximum possible torque

C00057

is reached at the motor shaft, the response set in

C00608

will be carried out (Lenze setting: "0: No Reaction").
If the activated monitoring is tripped:

• The "

OT1: Maximum torque reached

" error message is entered into the Logbook.

• The bMctrlTorqueMax status output of the

LS_DeviceMonitor

system block will be set to TRUE.

5.10.9

Encoder open-circuit monitoring

When does the open-circuit monitoring system respond?
The open-circuit monitoring will trigger if

• an open circuit occurs in the encoder cable.
• an extreme overload (e.g. blocked motor shaft) occurs during the start-up phase of the motor.
• highly dynamic reversion of the motor occurs.

Which measured values lead to an actuation of the open-circuit monitoring system?
The following measured values checked for plausibility lead to an actuation of the open-circuit

monitoring system:

1. If the total deviation between actual speed and setpoint speed is higher than f = 40 Hz for a time

> 0.1 s .

2. If the sign of the injected frequency and the actual speed is not the same, the I

max

controller is

active and this status is active for 0.1 s. Usually this is the case when A/B tracks are reversed.

Note!

In the Lenze setting (

C00608

= "0: No Reaction"), the maximum torque monitoring is not

activated!

Note!

In the Lenze setting (

C00586

= "1: Fault"), open-circuit monitoring of the encoder is

activated!