Lp1: motor phase failure [xx.0123.00145, Sd3: feedback system open circuit [xx.0123.00205, An01: ain1_i < 4 ma [xx.0125.00001 – Lenze E84DSxxx User Manual
Page 362: Io11: digout level [xx.0125.00011, Lp1: motor phase failure, Sd3: open circuit - feedback system, Xx.0125.00001, Xx.0125.00011, Xx.0123.00145, Xx.0123.00205

9
Diagnostics & error management
9.10
Error messages of the operating system
362
Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
LP1: Motor phase failure [xx.0123.00145]
SD10: Speed limit for feedback system 12 [xx.0123.00200]
SD3: Feedback system open circuit [xx.0123.00205]
An01: AIN1_I < 4 mA [xx.0125.00001]
Io11: DigOut level [xx.0125.00011]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Motor phase failure - power section
• This error message is displayed if a motor phase
carries less current of one half-wave than set in
.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Check the trigger threshold (
).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Maximally permissible speed of the feedback system
connected to DI1/DI2 reached.
Reduce speed of the rotation shaft/feedback system.
n
encoder
<= (f
max
x 60) / encoder increment
(for f
max
= 10 kHz)
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has detected open circuit in the feedback
system.
Check wiring of the feedback system and the
corresponding terminals.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Open-circuit monitoring for analog input 1 has tripped.
• Only if the analog input has been configured as a
current loop of 4 ... 20 mA (
= 2).
• Check wiring of the analog X3/A1I input terminal for
open circuit.
• Check minimum current values of the signal sources.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The actual level of a digital output does not correspond
to the setpoint level.
• Check wiring of the digital output terminal for short
circuit to earth.
• Check whether the digital output terminal is by
mistake triggered externally with a HIGH signal
although a LOW signal should be output.