1 parameterising digital inputs as encoder inputs, Parameterising digital inputs as encoder inputs, 5motor control (mctrl) – Lenze E84DSxxx User Manual
Page 167

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
167
5
Motor control (MCTRL)
5.8
Encoder/feedback system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.8.1
Parameterising digital inputs as encoder inputs
The function of the digital inputs DI1/DI2 is defined in
.
To be able to use the digital inputs as encoder inputs, select 2, 3 or 4 (Lenze recommendation: 2) in
depending on the input terminals used.
Related topics:
Using DI1(5) and DI2(6) as frequency inputs
Selection in
Function
2: (DI1/DI2)=FreqIn12 (2-track)
DI1 and DI2 = 2-track frequency input
• Permits a two-track evaluation of the encoder including correct
detection of the direction of rotation.
3: (DI1/DI2=+-)=FreqIn12
DI1 = 1-track frequency input
DI2 = direction
4: DI1=CountIn1 | DI2=In2
DI1 = counter input
DI2 = digital input
Danger!
For single-track evaluation, make sure that the sign is correctly specified. Otherwise, the
motor may overspeed.
Note!
If the digital inputs are parameterised as encoder inputs, the corresponding output
signals (bIn1/bIn2) at the
system block are automatically set to FALSE.
The wiring diagram and the assignment of the input terminals can be found in the 8400
protec hardware manual.
• The hardware manual has been stored in electronic form on the data carrier supplied
with the 8400 drive controller.