3 avoiding thermal overload of the brake resistor, Avoiding thermal overload of the brake resistor, Avoiding thermal – Lenze E84DSxxx User Manual

Page 178: Overload of the brake resistor, 5motor control (mctrl)

Advertising
background image

5

Motor control (MCTRL)

5.9

Braking operation/brake energy management

178

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

For sensorless vector control (SLVC):

• Set reduced brake chopper threshold (

C00174

) to approx. 70 V.

• Set additive speed (

C00987

) to 2 ... 4-fold rated slip speed.

• Adapt the deceleration ramp so that the deceleration time is slightly below (10 ... 30 %)

the deceleration time that can be realised with the inverter motor brake.

5.9.3

Avoiding thermal overload of the brake resistor

• Parameterisation of an error response in

C00574

and evaluation of the parameterised error

message within the application or within the machine control system.

• See chapter entitled "

Brake resistor monitoring (I2xt)

".

( 184)

• External interconnection using the thermal contact on the brake resistor (e.g. supply

interruption via the mains contactor and activation of the mechanical brakes).