C00905 | motor phase direction of rotation, C00909 | speed limitation, C00910 | frequency limitation – Lenze E84DSxxx User Manual
Page 617: C00915 | motor cable length, C00915, Motor ca, C00909/1, C00909/2, C00910/1, C00910/2

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
617
15
Parameter reference
15.2
Parameter list | C00905
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00905
C00909
C00910
C00915
Parameter | Name:
C00905 | Motor phase direction of rotation
Data type: UNSIGNED_8
Index: 23670
d
= 5C76
h
To correct such misconnected motor phases, the rotating field of the controller's output can be reversed by selecting
"1: Inverted". In this case, a phase will be reversed at the output of the inverter.
Selection list
(Lenze setting printed in bold)
0 not inverted
1 inverted
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00909 | Speed limitation
Data type: INTEGER_16
Index: 23666
d
= 5C72
h
Max. positive/negative speed for all motor control modes
Setting range
(min. value | unit | max. value)
0.00
%
175.00
Subcodes
Lenze setting
Info
C00909/1
120.00 %
Max. pos. speed
C00909/2
120.00 %
Max. neg. speed
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00910 | Frequency limitation
Data type: UNSIGNED_16
Index: 23665
d
= 5C71
h
Max. positive/negative output frequency for all motor control modes
Setting range
(min. value | unit | max. value)
0
Hz
1000
Subcodes
Lenze setting
Info
C00910/1
1000 Hz
Max. pos. output frequency
C00910/2
1000 Hz
Max. neg. output frequency
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00915 | Motor cable length
Data type: UNSIGNED_16
Index: 23660
d
= 5C6C
h
Single motor cable length for calculating the motor cable resistance
• The calculated motor cable resistance is displayed in
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
m
1000.0 5.0 m
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10