C00905 | motor phase direction of rotation, C00909 | speed limitation, C00910 | frequency limitation – Lenze E84DSxxx User Manual

Page 617: C00915 | motor cable length, C00915, Motor ca, C00909/1, C00909/2, C00910/1, C00910/2

Advertising
background image

Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05

617

15

Parameter reference

15.2

Parameter list | C00905

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00905

C00909

C00910

C00915

Parameter | Name:

C00905 | Motor phase direction of rotation

Data type: UNSIGNED_8

Index: 23670

d

= 5C76

h

To correct such misconnected motor phases, the rotating field of the controller's output can be reversed by selecting

"1: Inverted". In this case, a phase will be reversed at the output of the inverter.
Selection list

(Lenze setting printed in bold)

0 not inverted
1 inverted

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00909 | Speed limitation

Data type: INTEGER_16

Index: 23666

d

= 5C72

h

Max. positive/negative speed for all motor control modes
Setting range

(min. value | unit | max. value)

0.00

%

175.00

Subcodes

Lenze setting

Info

C00909/1

120.00 %

Max. pos. speed

C00909/2

120.00 %

Max. neg. speed

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00910 | Frequency limitation

Data type: UNSIGNED_16

Index: 23665

d

= 5C71

h

Max. positive/negative output frequency for all motor control modes
Setting range

(min. value | unit | max. value)

0

Hz

1000

Subcodes

Lenze setting

Info

C00910/1

1000 Hz

Max. pos. output frequency

C00910/2

1000 Hz

Max. neg. output frequency

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00915 | Motor cable length

Data type: UNSIGNED_16

Index: 23660

d

= 5C6C

h

Single motor cable length for calculating the motor cable resistance

• The calculated motor cable resistance is displayed in

C00917

.

Setting range

(min. value | unit | max. value)

Lenze setting

0.0

m

1000.0 5.0 m

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 10