5motor control (mctrl) – Lenze E84DSxxx User Manual
Page 194

5
Motor control (MCTRL)
5.11
Internal interfaces | System block "LS_MotorInterface"
194
Lenze · 8400 protec StateLine · Reference manual · DMS 4.2 EN · 03/2013 · TD05
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
nMotorVoltage_a
INT
Current motor voltage/inverter output voltage
• Scaling: 16384 ≡ 1000 V
bQspActive
BOOL
"Quick stop active" status signal
TRUE Quick stop is active
bAutoDCBActive
BOOL
"Automatic DC-injection braking active" status signal
TRUE Automatic DC-injection braking is active
bIdentificationActive
BOOL
"Motor parameter identification active" status signal
Automatic motor data identification ( 104)
TRUE Motor parameter identification is active
bFlyingSyncActive
BOOL
"Flying restart function active" status signal
Flying restart function ( 152)
TRUE Flying restart function is active
bHlgLoad
BOOL
Control signal for an additional loading function of the ramp function generator
.bExternalCINH
• To enable the ramp function generator to follow automatically when the
controller is inhibited, for jerk-free setpoint connection.
TRUE Set the ramp function generator to a setpoint of nHlgSetValue_a
nHlgSetValue_a
INT
Setpoint for an additional loading function of the ramp function generator
.nCInhVal_a
• For speed-controlled drive tasks, the current actual speed value (e.g. in case of an
active pulse inhibit, flying restart function, controller inhibit) is provided at this
output.
• Scaling: 16384 ≡ 100 % reference speed (
bHlgStop
BOOL
Control signal for stopping the ramp function generator (
)
TRUE Stop the ramp function generator
Identifier
DIS code | data type
Value/meaning