5 rly out connector details, 2 ) rly out connection cable – Yaskawa MP2300S Basic Module User Manual

Page 114

Advertising
background image

3.2 Basic Module Connections

3.2.5 RLY OUT Connector Details

3-23

Mounting and Wiring

3.2.5 RLY OUT Connector Details

The RLY OUT connector is a terminal for outputting state and NO contact relay output. A circuit between terminals is
short-circuited when RDY LED is lit, and opens when it is unlit.

Note: A state when RDY LED is lit indicates that a controller is operating normally. It does not indicate that an

user program is running.

( 1 ) RLY OUT Connector Specifications and Pin Arrangement

The following table provides the RLY OUT connector specifications.

The following table shows the RLY OUT connector pin arrangement.

The following table provides the RLY OUT connector contact ratings.

( 2 ) RLY OUT Connection Cable

For the RLY OUT connection cable, use a cable of line size AWG28 to AWG14 (0.08 mm

2

to 1.5 mm

2

), maximum

sheath diameter

φ3.4 mm.

The manufacturing procedures for the RLY OUT connection cable and the 24-VDC power supply cable are similar.

Name

Connector

Name

Number

of Pins

Connector Model

Module Side

Cable Side

Manufacturer

RLY OUT

RLY OUT

2

734-162

734-YE102

Wago Corporation

Pin Number

Signal Name

Description

1

OUT

• Operating normally: Short-circuit
• Error occurred: Opened

2

OUT

Input Voltage

Current Capacity

24 VDC

0.5 A (resistance load)

0.25 A (induced load)

125 VAC

0.4 A (resistance load)

0.2 A (induced load)

RLY

OUT

Advertising