Appendix G MSG-SND/MSG-RCV Functions (Ethernet)

G.2 Message Receive Function (MSG-RCV)

A-92

( 1 ) MEMOBUS Parameter List

* It is IN/OUT for MODBUS/TCP.

Note: IN: Input, OUT: Output, SYS: For system use

( 2 ) Non-procedural Parameter List

Note: IN: Input, OUT: Output, SYS: For system use

Param No.

IN/OUT

Contents

Description

00

OUT

Process result

Outputs process results.

01

OUT

Status

Outputs the status of the communication device.

02

IN

Connection number

Specifies the remote source.

03

OUT

Option

Outputs a unique value for each communication device.

04

OUT

Function code

Outputs a function code requested from the transmission side.

05

OUT

*

Data address

Outputs the start address of data requested from the transmission
side.

06

OUT

Data size

Outputs the read/write data size requested from the transmission
side.

07

OUT

Remote CPU number

Outputs the remote CPU number.

08

IN

Coil offset

Sets the coil’s offset word address.

09

IN

Input relay offset

Sets the offset word address of an input relay.

10

IN

Input register offset

Sets the offset word address of an input register.

11

IN

Holding register offset

Sets the offset word address of a holding register.

12

IN

Write range LO

Sets the start address for a write range.

13

IN

Write range HI

Sets the last address for a write range.

14

SYS

Reserved 1

15 to 16

SYS

Reserved 2

Param No.

IN/OUT

Contents

Description

00

OUT

Process result

Outputs the process results.

01

OUT

Status

Outputs the status of the communication device.

02

IN

Connection number

Specifies the remote source.

03

OUT

Not used

04

OUT

Not used

05

OUT

Not used

06

OUT

Data size

Outputs the write data size requested from the transmission side.

07

OUT

Not used

08 to 11

IN

Not used

12

IN

Register offset

Sets the register's offset word address.

13

IN

Write range HI

Sets the last address for a write range.

14

SYS

Reserved 1

15 to 16

SYS

Reserved 2