8.2 Regular Inspections

8-3

Maintenance and Inspection

8.2 Regular Inspections

This section explains inspection items that must be performed once or twice every six months to one year.

Inspections must also be performed when the equipment is relocated or modified or when the wiring is changed.

Œ

Do not replace the built-in fuse.
If the customer replaces the built-in fuse, the MP2300S may malfunction or break down.
Contact your Yaskawa representative.

PROHIBITED

No.

Inspection Item

Inspection Details

Criteria

Action

1

Operating
Environment

Ambient Temperature

Check the temperature and
humidity with a thermometer
and hygrometer, respectively.
Check for corrosive gases.

0

°C to 55°C

If the MP2300S is used
inside a panel, treat the tem-
perature inside the panel as
the ambient temperature.

Ambient Humidity

30% to 95% RH

Atmosphere

There must be no corrosive
gases.

2

Power
Supply
Voltage
Check

PS Module

Measure the voltage between
24-VDC terminals.

19.2 to 28.8 VDC

Change the power supply as
necessary.

3

Installation
Conditions

Looseness and
Excess Play

Attempt to move the Module.

The Module must be secured
properly.

Retighten the screws.

Dust and Other For-
eign Matter

Visually check.

The Module must be free
from dust and other foreign
matter.

Clean.

4

Connection
Conditions

Check the Terminal
Screws for Looseness.

Check by retightening the
screws.

The screws must be tight.

Retighten.

Gap between Crimp
Terminals

Visually check.

There must be an appropriate
gap between the terminals

Correct.

Looseness of
Connectors

Visually check.

The screws must be tight.

Retighten the connector set
screws.

5

Battery

Check the BAT indicator on
the front panel of the Basic
Module.

The BAT indicator must be
not lit.

If the BAT indicator is lit,
replace the battery.