Yaskawa MP2300S Basic Module User Manual
Page 228

6.2 Communication with Other MP Series
6.2.3 When the MP2300S Acts as Master (I/O message communication function is used)
6-39
Built-in Ethernet Communications
4.
Set a communication setting in the I/O Message Communication Easy Setting Window.
How to set up in the I/O Message Communication Easy Setting Window
c Set Port No. of the MP2300S side (“10005, 10006,” X for example).
d Select Extended MEMOBUS for Communication Protocol Type, and click the Default Button.
Caution
When the communication protocol is Extended MEMOBUS, the register type that can select both read and write is fixed at the
Holding Register (MW).
e Select Connect Type (TCP, for example).
f Select Code (BIN, for example).
g Set Remote IP Address for the other device (MP2300) to be connected (“192.168.001.002,” for example).
h Set Port No. of the other device (MP2300) to be connected (“10005, 10006,” for example).
Caution
In I/O message communication, as a message is transmitted from each port number for register read/write, a connected remote
device needs the message receive functions to receive two messages.
f
g
h
ik
j
c
l
h
c
d e